R48-100LFP ESS Status Indicator

Modified on Tue, 30 Jun at 2:48 PM

STATUS INDICATOR INSTRUCTIONS

The Rolls R48-100LFP ESS batteries come equipped with 6 LED lights located on the rear of the unit. Each light’s function, varying status indications and position on the battery can be seen in the table below. For more information on status alarms refer to BMS Protection Systems. For more information on LED Indicator SOC (state of charge) see the SOC Indication section above.

Note: ‘Warning’ includes cell imbalance, high or low voltage, high current, high or low temperature.


Mode

Status

Run

Alarm

LED Indicator

Information

A picture containing night sky

Description automatically generated

A picture containing night sky

Description automatically generated

A picture containing night sky

Description automatically generated

A picture containing night sky

Description automatically generated

A picture containing night sky

Description automatically generated

A picture containing night sky

Description automatically generated

Power off

/

Off

Off

Off

Off

Off

Off

/

Standby

Normal

Flash - 1

Off

Indicating level of charge

/

Warning

Flash - 1

Flash - 3

/

Charge

Normal

On

Off

Indicating level of charge 

Full charge Flash - 2

Warning

On

Flash - 3

Overcurrent 

Flash - 1

Off

Charging Stopped

Discharge

Normal

Flash - 3

Off

Indicating level of charge 

/

Warning

Flash - 3

Flash - 3

/

Undervoltage

Off

Flash - 3

Off

Off

Off

Off

Discharging Stopped

Overcurrent 

Off

On

Off

Off

Off

Off

Discharging Stopped

Temp. Protection

Outside operating temp.

Off

On

Off

Off

Off

Off

Battery Disconnected

Failure

See below 

Off

On

Off

Off

Off

Off

Battery Disconnected

 FLASH INDICATION

Flash

ON

OFF

A picture containing night sky

Description automatically generated

Icon

Description automatically generated

Flash - 1

0.25s

3.75s

Flash - 2

0.5s

0.5s

 Flash - 3 

0.5s

1.5s




BATTERY LIMIT

PROTECTION

RESET METHOD

COMMENTS

Cell/Pack Overvoltage

Charge Interruption

Discharge will resume once all cell voltages return to the recovery range or a sufficient discharging current is detected.


Cell/Pack Undervoltage

Discharge Interruption

Discharge will resume once all cell voltages return to the recovery range or a sufficient charging current is detected.

Recharge the system in a timely manner to avoid damage due to extended overdischarge

Extended Pack Undervoltage

(Stored While Empty)

Battery Cannot be Recovered

Always charge

R48-100LFP ESS

batteries within 72 hours

of full discharge

-

Pack Overcurrent 

Charge and Discharge Interruption

Automatically reset after time delay

If occurring more than 3 times consecutively, charge is required.

High temperature at BMS or Cell

Charge and Discharge Interruption

Automatically reset after cooling

BMS will display alarm when approaching disconnect.

Low temperature at BMS or Cell

Charge Interruption

Automatically reset after warming

BMS will display alarm when approaching disconnect.

Extreme low temperature at BMS or Cell

Charge and Discharge Interruption

Automatically reset after warming

BMS will display alarm when approaching disconnect.

Short circuit or reverse polarity 

Charge Interruption

Charge to release or manually press reset 

Misuse in this way will void the warranty.

Sleep mode

-

Charge, press reset, or restart to activate 

BMS will enter sleep mode to reduce power consumption.

Was this article helpful?