Configuring Legacy Inverters with LFP Batteries

Modified on Thu, 12 Nov at 3:04 PM

Open-Loop Integration – Field Experience and Recommendations


My experience with LFP batteries and legacy inverter/charger equipment has been mixed. Some equipment works reasonably well, while other equipment presents challenges that require careful configuration and ongoing customer involvement.

In many cases, these systems can be configured to work with LFP batteries in an open-loop configuration. However, there are limitations, particularly when it comes to charging algorithms, voltage regulation, battery monitoring, and maintaining balance between parallel batteries.

The following recommendations are based on my experience working with these systems in the field.


1. Magnum Configuration Requirements

With Magnum equipment, I haven't encountered too many issues connecting LFP batteries in an open-loop configuration, provided a few precautions are taken.

  1. Remote Display: You must have either the Advanced Remote or the Advanced Router Remote.

  2. BMK (Battery Monitor Kit): Do not use the BMK. I've found that it barely works reliably with lead-acid batteries. With LFP, the errors and warnings it generates can drive both you and your customer crazier than you already are.

  3. PT-100 Charge Controller: If you're using a PT-100 with a Magnum inverter, you cannot link the inverter charging settings to the charge controller settings. Disable this feature in Menu 02E.

  4. Battery Programming: Program the system using Custom Battery settings. I've found this necessary even when a Lithium setting is available. Most preprogrammed lithium profiles are designed for 15-cell-series batteries rather than 16-cell-series batteries.

2. Charging Configuration

I generally recommend the following charging configurations:

  • Solar Charge Controllers: Two-stage charging.

  • Inverters/Chargers: Three-stage charging.

Absorb timer settings are particularly important.

As a general starting point, allow at least 20–30 minutes of absorb time per parallel battery in the system.

For larger systems with relatively low charging current (less than 8–10% of the bank's C20 capacity), you may need to increase absorb time to as much as one hour per parallel battery.

Important: Do not terminate charging based on End Amps or SOC%. Terminate charging only upon completion of the programmed Absorb Done timer.


End Amps and SOC% accuracy are not sufficiently reliable in many of these systems to use these features for LFP charging. For that matter, I've found similar limitations when using them with lead-acid batteries.


3. Battery Temperature Compensation (BTS)

Disconnect the BTS from the inverter and charge controller. Do not allow battery temperature compensation to operate.

Even with the BTS disconnected, Magnum's output voltage regulation can introduce overvoltage errors with LFP batteries.

Slightly reducing the absorb voltage target can help minimize these errors. However, there is a trade-off: lowering the charging voltage can make it more difficult for the batteries to reach a full charge and balance properly.

This can increase voltage and SOC differences between batteries, potentially requiring additional manual balancing of the battery bank.


4. Low Battery Disconnect Settings

Set Low Battery Disconnect at or just above nominal battery voltage.

Recommended starting points:

System VoltageLow Battery Disconnect
12V12.0–12.2V
24V24.0–24.4V
48V48.0–48.4V

These are starting points and should be adjusted according to the battery manufacturer's recommendations and the actual system operating requirements.


5. Routine Battery Monitoring and Maintenance

Customers should periodically check the SOC% and individual battery voltages of all parallel battery stacks.

I recommend performing these checks every 30–60 days, preferably after the system has completed a full 100% charge.

Pay particular attention to the following:

  • SOC% differences between individual batteries.

  • Resting voltage differences between individual batteries.

If SOC% is more than 4–5% out of balance, or resting battery voltages differ by more than 0.3V, the batteries should be separated and individually charged to 100% to rebalance the bank.

The objective is to prevent small differences between batteries from developing into larger imbalances over time.


6. Other Legacy Inverter and Charger Manufacturers

OutBack Power

I've found that the OutBack FM60, FM80, and FM100 charge controllers can be configured to work with LFP batteries.

OutBack GT Inverters: These do not work particularly well with lithium batteries. Their battery charging algorithm changes based on how quickly battery voltage rises. This can lead to inconsistent charging and balancing issues.

OutBack Radian Inverters: These can be programmed to work with LFP batteries.


However, I've found that pre-2008 OutBack inverters, for some reason, just don't like lithium batteries. Something in the firmware appears to cause the inverters to bypass absorption, which can lead to balancing issues.

Schneider Electric

Schneider equipment can also work with LFP batteries.

I generally configure the charging much like the Magnum recommendations:

  • Charge controllers operating in two-stage mode.

  • Inverter/chargers programmed for three-stage charging.

  • User-defined battery settings.

  • Carefully configured absorb voltage and timers.

Victron Energy

Victron equipment generally works well with LFP batteries.

I would again recommend using a user-defined battery profile and disabling adaptive charging.

The Magnum configuration outline above provides a good starting point for programming and maintaining these systems, although individual equipment settings and capabilities will vary.

Trace Engineering and Heart Interface

Even some of the older Trace Engineering and Heart Interface inverters can work with LFP batteries, provided you have control over the absorb timer settings.

Inverters such as the older UL, UX, DR, and Heart 458 models do not provide adequate control over absorb timer settings. This can lead to inconsistent charging and battery balancing issues.


7. Battery Monitoring Equipment

The battery monitoring equipment I've had the best experience with includes:

  • Victron BMV-712.

  • Victron BMV-712 Smart.

Traditional battery monitoring equipment from Magnum (BMK), Schneider, and OutBack (FNDC) is not ideal for LFP applications.

These products were largely designed around lead-acid battery characteristics. Their SOC calculations and monitoring algorithms are not necessarily suited to LFP batteries.

I've encountered inaccurate SOC readings, along with numerous errors and warnings, particularly as battery SOC drops below 50%.

For this reason, I generally prefer monitoring the battery manufacturer's individual battery data and voltage readings rather than relying exclusively on the inverter's battery monitor.


8. The Bottom Line

If you have a customer who is willing to work with you, learn the equipment, and perform some basic system monitoring and maintenance, you can configure much of this legacy equipment to work with lithium batteries.

However, if you have a customer who isn't willing to learn the system, or simply doesn't have the ability or interest to monitor and maintain it, I would strongly recommend going with a closed-loop system.

There is another consideration with much of the legacy equipment: charging voltage regulation.

Many of these older inverters and charge controllers simply do not regulate their charging output particularly well. Their output can be electrically noisy and can generate high-voltage errors and warnings with LFP batteries.

This can happen even when the programmed charging voltages are correct:

  • 12V system: 14.4V

  • 24V system: 28.8V

  • 48V system: 57.6V

The pulse-width modulation (PWM) of the charging output can produce voltage fluctuations that trigger annoying high-voltage errors and warnings in the battery management system.

Ultimately, just because you can make legacy equipment work with LFP batteries doesn't necessarily mean you should.

Open-loop systems require more attention, more customer education, and a better understanding of the equipment's limitations. Closed-loop systems generally provide a much more straightforward installation and support experience, particularly for customers who want a system that simply works without having to become battery technicians themselves.